.TH "MODBUS/TCP Protocol" 3 "20 Oct 2006" "Modbus Slave C++ Library" \" -*- nroff -*-
.ad l
.nh
.SH NAME
MODBUS/TCP Protocol \- 
.SH "Detailed Description"
.PP 
The Server Engine of the MODBUS/TCP slave protocol is implemented in the class \fBMbusTcpSlaveProtocol\fP. 
.PP
It provides functions to start-up and to execute the server engine. This server engine can handle multiple master connections and is implemented as a single threaded TCP server. Upon receipt of a valid master query the server engine calls Data Provider methods to exchange data with the user application. For a more detailed description which Modbus data and control functions have been implemented in the server engine see section \fBServer Functions common to all Protocol Flavours\fP.
.PP
\fBNote:\fP
.RS 4
If the configured TCP port is below IPPORT_RESERVED (usually 1024), the process has to run with root privilege! This applies if you are using the default MODBUS/TCP port 502.
.RE
.PP
See section \fBThe MODBUS/TCP Protocol\fP for some background information about MODBUS/TCP.
.PP
See section \fBUsing MODBUS/TCP Protocol\fP for an example how to use the \fBMbusTcpSlaveProtocol\fP class. 
.PP
.SS "Classes"

.in +1c
.ti -1c
.RI "class \fBMbusTcpSlaveProtocol\fP"
.br
.RI "\fIMODBUS/TCP Slave Protocol class. \fP"
.in -1c
.SS "Defines"

.in +1c
.ti -1c
.RI "#define \fBMAX_CONNECTIONS\fP   16"
.br
.RI "\fIMaximum concurrent TCP/IP connections handled by server engine. \fP"
.in -1c